ILDCP Series Models: These are UL listed 497B in-line series screw terminal multi-stage hybrid devices. These
units are designed not only to protect equipment but also reduce the
incidence of false alarms due to its close clamping ability at
high-induced voltages. There is a ground lug provided. Only use if you have a common ground i.e. single ground for entire system to prevent ground loops.
FA-60: 60
Volts DC to be used on the initiating circuits and addressable loops
operating above 24V DC (38V DC) that are drawing less than 1 amp.
|
Specifications/Operating: |
|
|
|
|
|
Maximum Operating Voltage: |
48 Volts DC |
|
Typical Leakage Current: |
< 5u Amps |
|
Maximum Data Rate: |
22 Kbs |
|
Operation Temperature: |
- 40 - + 85 C |
|
Connection: |
Dual Terminal Blocks |
|
Lines Protected: |
One Pair |
|
Installation Configuration: |
In-Line Series |
|
|
|
|
Specifications/Electronic: |
|
|
|
|
|
Maximum Surge Current (8x20us): |
10,000 Amps Per line |
|
Maximum Surge Voltage (1.2x50us): |
6,000 Volts |
|
Capacitance: |
<250 pf |
|
Clamping Voltage: |
60 Volts |
|
Clamping Response Time: |
<5 Nanoseconds |
|
Voltage: |
Voltage sensitive |
|
Power Dissipation: |
60,000,000 VA |
|
UL497 B |
E158611 |
|
Pass Voltage (ANSI/IEEE B3 Impulse): |
60 Volts |
|
First Stage Power Dissipation (8x20us): |
10,000 Amps |
|
Dimension: |
Depth: 1" Width: 2" Length: 1 ½" Tabs: ½" each |
E-Clips surge suppressors have a Lifetime Product Warranty. Please see warranty statement for complete product warranty information.