120 HWCP 20M
120 Volt AC 3-Wire 15-20 Amp (Series)
|
Specifications – Operating: |
|
|
|
|
|
Maximum Operating Voltage: |
120 Volts AC |
|
Typical Leakage Current: |
None |
|
Operation Temperature: |
-40 to + 85° C |
|
Connection: |
Hardwired |
|
Lines Protected: |
L/N, L/G, N/G |
|
Installation Configuration: |
In-Line Series |
|
|
|
|
Specifications – Electronic: |
|
|
|
|
|
Maximum Surge Current (8x20µs): |
6,000 Amps Total |
|
Maximum Surge Voltage (1.2x50µs): |
3,000 Volts |
|
Clamping Voltage: |
130 Volts RMS |
|
Clamping Response Time: |
<5 nanoseconds |
|
Maximum Line Voltage: |
15 Amps @ 120 VAC 45/60 Hz |
|
Voltage: |
Voltage Sensitive |
|
Operation Indicator: |
Yes - LED |
|
Power Dissipation (8x20µs): |
750 Joules or (20,000,000 VA) |
|
UL Recognized Component: |
TVSS Device UL File E121637 |
|
Failure Mode: |
Fails Safe (Open) |
|
Dimensions: |
Depth: 1.5†Width 3†Length 5†Tabs .5†|
|
Weight: |
Approximately 1 Lb. |
IEEE 587 (ANSI C62.41 – 1980)
Dynamic Clamping Voltages (V peak @ 90 degree phase angle)
ANSI/IEEE Category B3 Impulse: L/N L/G N/G
6,000 Volts @ 1.2X50µs 220V Peak 265V Peak 207V Peak
3,000 Amps @ 8X20µs (154V RMS) (185V RMS) (145V RMS)
E-Clips surge suppressors have a Lifetime Product Warranty. Please see warranty statement for complete product warranty information.