120 HWCP 20M - 120 Volt AC 3-Wire - 15-20 Amp (Series)

120 HWCP 20M: If your power side
of the system requires a hardwire connection, this 120 Volt AC 3-Wire
Single Phase (15-20 Amp) device should be installed as close as
possible to the equipment being protected. This
is an in-line series (AC) surge suppressor and is designed to stop
surges from getting to the PLC – (Mother Board/Computer Board). The 120HWCP20M has a maximum current draw of 15-20 amps and provides both common and normal three-phase noise filtration. UL 1449 listed and rated 400V peak for L-N, L-G, N-G.
|
Specifications – Operating: |
|
|
Maximum Operating Voltage: |
120 Volts AC |
|
Typical Leakage Current: |
None |
|
Operation Temperature: |
- 40 to + 85° C |
|
Connection: |
Hardwired |
|
Lines Protected: |
L/N, L/G, N/G
|
|
Installation Configuration: |
In-Line Series |
|
|
|
|
Specifications – Electronic: |
|
|
Maximum Surge Current (8x20µs): |
6,000 Amps Total |
|
Maximum Surge Voltage (1.2x50µs): |
3,000 Volts |
|
Clamping Voltage: |
130 Volts RMS |
|
Clamping Response Time: |
<5 nanoseconds |
|
Maximum Line Voltage: |
15-20 Amps @ 120 VAC 45/60 Hz |
|
Voltage: |
Voltage Sensitive |
|
Operation Indicator: |
Yes - LED |
|
Power Dissipation (8x20µs): |
750 Joules or (20,000,000 VA) |
|
UL Recognized Component: |
TVSS Device UL File E121637 |
|
Failure Mode: |
Fails Safe (Open) |
|
Dimensions: |
Depth: 1.5†Width 3†Length 5†Tabs .5†|
|
Weight: |
Approximately 1 Lb. |